id
stringlengths
15
15
type
stringclasses
9 values
module
stringclasses
179 values
module_title
stringclasses
178 values
text
stringlengths
56
9.03k
ch_225dbdd2ca10
intro
mod_21_relay
Distance Line Protection Relays
One of the more complicated legacy protective relay technologies is the *impedance-based distance relay*, designed to determine the proximity of a line fault by means of sensing impedance based on simultaneous voltage and current measurements. This is a very versatile type of protection scheme, but also fairly difficul...
ch_ce03f5c14337
tutorial
mod_21_relay
Distance Line Protection Relays
A form of protection against faults on long-distance power lines is called *distance* relaying, so named because it is actually able to estimate the physical distance between the relay's sensing transformers (PTs and CTs) and the location of the fault. In this way, it is a more sophisticated form of fault detection tha...
ch_950c80ea0e78
tutorial
mod_21_relay
Distance Line Protection Relays
In order to understand the rationale for distance relaying on transmission lines, it is useful to recognize the limitations of simple overcurrent (50/51) protection. Consider this single-line diagram of a transmission line bringing power from a set of bus-connected generators to a substation at some remote distance. Fo...
ch_bd8bef7f9b30
tutorial
mod_21_relay
Distance Line Protection Relays
This causes a problem for the "reach" of the overcurrent relay controlling breaker "F." With reduced current capacity from the generator bus, the same relay setting that worked well to protect the transmission line zone will now be too high for faults lying toward the far end of that line. In other words, the overcurre...
ch_2d7695ad9d81
tutorial
mod_21_relay
Distance Line Protection Relays
Capacitance, inductance, and resistance are all naturally present along miles of power line conductors: capacitance due to electric fields existing within the separation of the lines from one another and from earth ground by the dielectric of porcelain insulators and air; inductance due to the magnetic fields surroundi...
ch_fa71c21f9bfb
tutorial
mod_21_relay
Distance Line Protection Relays
Oscilloscope displays showing the raw voltage and current waveforms are clumsy representations of line impedance. Better visual representations for impedance exist, the most popular being a *phasor diagram* for line impedance with resistance ($R$) on the horizontal axis and reactance ($X$) on the vertical axis, commonl...
ch_ac78df322404
tutorial
mod_21_relay
Distance Line Protection Relays
A primitive electromechanical impedance relay design for detecting faults along long-distance transmission lines uses a simple balance-beam mechanism to sense when the ratio of line current to line voltage ($I \over V$) becomes excessive. It will trip if ever the impedance became too small (i.e. too much $I$ and too li...
ch_448550f781bc
tutorial
mod_21_relay
Distance Line Protection Relays
This relay's reach is defined as any impedance falling within the circle, just as we defined the reach of the impedance relay. The difference here, of course, is that the "mho" distance relay is entirely insensitive to conditions within the lower quadrants of the R-X diagram. With the addition of the phase-shifting ca...
ch_8a2b243735c3
question
mod_21_relay
Distance Line Protection Relays
Correct analysis and diagnosis of electric circuits begins with a proper understanding of some basic concepts. The following is a list of some important concepts referenced in this module's full tutorial. Define each of them in your own words, and be prepared to illustrate each of these concepts with a description of a...
ch_f0ecae7e784e
question
mod_21_relay
Distance Line Protection Relays
A powerful computational tool you are encouraged to use in your work is a *spreadsheet*. Available on most personal computers (e.g. Microsoft Excel), *spreadsheet* software performs numerical calculations based on number values and formulae entered into cells of a grid. This grid is typically arranged as lettered colum...
ch_3b484a6d9e87
question
mod_21_relay
Distance Line Protection Relays
Note how the square-root term ($y$) is calculated in cell `C1`, and the denominator term ($z$) in cell `C2`. This makes the two final formulae (in cells `B1` and `B2`) simpler to interpret. The positioning of all these cells on the grid is completely arbitrary [Footnote: My personal preference is to locate all the "giv...
ch_17757d5b461b
intro
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Some of the simplest types of digital communication networks used to connect different computer devices together are defined by the EIA (Electronic Industry Alliance) and TIA (Telecommunications Industry Alliance) groups, under the numerical labels 232, 422, and 485. This module explores these three network types. Imp...
ch_e4fc5e75a9bd
intro
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
The following list cites concepts related to this module's topic that are easily misunderstood, along with suggestions for properly understanding them: - **Shift registers** -- widely used in serial data communication, shift registers operate by "shifting" the locations in which bit-states are held by semiconductor fl...
ch_dafb51ae314f
case_tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
In the following illustrations we will show three examples of UART serial data signals representing eight-bit binary numbers, assuming the use of positive DC source voltage for "idle" and logical "1" states and zero voltage for logical "0" states [Footnote: Note how this "positive" logic is consistent with most digital...
ch_1b346c310e84
case_tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
A digital oscilloscope configured for single-sweep mode may be used to capture the EIA/TIA-232 serial data stream transmitted by a personal computer if measuring voltage between the PC's "transmit" and "ground" pins (3 and 5, respectively): [Figure image_5507: drawing; labels: 2, 5, EIA/TIA-232, male connector, Pin 2 ...
ch_74347773ffc8
case_tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
An interesting circuit utilizing serial data communication is shown here, where a U-Blox model SAM-M8Q Global Positioning System (GPS) radio receiver module interprets radio signals from satellites in geosynchronous orbit and generates a stream of positioning data sent out of its UART "transmit" port. The GPS receiver ...
ch_1ab45a3ef2d3
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Digital data is comprised of *bits* of information, each bit being either a 1 or a 0, a high or a low, a true or a false. Collections of bits are generally known as *words*, although some specific numbers of them have unique names, such as a *byte* for an 8-bit word, or a *nybble* for a 4-bit word. One way to communic...
ch_afd9fa61064f
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
The EIA/TIA-232C standard, formerly [Footnote: The designation of "RS-232" has been used for so many years that it still persists in modern writing and manufacturers' documentation, despite the official status of the EIA/TIA label. The same is true for EIA/TIA-422 and EIA/TIA-485, which were formerly known as RS-422 an...
ch_d513125967d2
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
| **Pin number** | **DTE assignment** | **Abbreviation** | |---|---|---| | 1 | Carrier Detect | CD | | **2** | **Received Data** | **RD** | | **3** | **Transmitted Data** | **TD** | | 4 | Data Terminal Ready | DTR | | **5** | **Signal Ground** | **Gnd** | | 6 | Data Set Ready | DSR | | 7 | Request To Send | RTS | | 8 |...
ch_92e1375bea02
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Similarly, if we wish to have an EIA/TIA-232 communicate with itself, we may connect a *loopback* jumper wire from its TD pin to its RD pin as such: [Figure image_7361: drawing; labels: TD, RD, Gnd, Computer, (DTE device), 2, 3, 5, Loopback jumper] For example, if the device in question is a terminal with keyboard an...
ch_7c42e8aab752
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
The next two network standards [Footnote: Former labels for EIA/TIA-422 and EIA/TIA-485 were RS-422 and RS-485, respectively. These older labels persist even today, to the extent that some people will not recognize what you are referring to if you say "EIA/TIA-422" or "EIA/TIA-485."] are less comprehensive than EIA/TIA...
ch_d633c435b51f
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
The maximum recommended cable length for both EIA/TIA-422 and EIA/TIA-485 networks is 1200 meters, which is greater than half a mile [Footnote: 1200 meters is the figure commonly cited in technical literature. However, Park, Mackay, and Wright, in their book *Practical Data Communications for Instrumentation and Contro...
ch_4637b9730b65
tutorial
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
The following schematic diagram shows the equivalent circuit of an EIA/TIA-485 transmitter [Footnote: A full EIA/TIA-485 *transceiver* would also have a differential receiving amplifier paralleled to the same pair of A/B terminals. That is not shown here since it's not necessarily relevant. It could also be that these ...
ch_6122e15e1bf3
derivation
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
ASCII characters consist of seven-bit digital words. The following table shows all 128 possible combinations of these seven bits, from `0000000` (ASCII "NUL" character) to `1111111` (ASCII "DEL" character). For ease of organization, this table's columns represent the most-significant three bits of the seven-bit word, w...
ch_a51430a21c1d
derivation
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Digital communication is a fairly complex topic, and there are a great many ways in which one digital device might communicate information to another. In order to help describe how different methods (protocols) function in forming a complete communication system, the *OSI Reference Model* was developed. This is not a s...
ch_78cad89f8c73
derivation
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Data communication networks based on differential voltage signals such as EIA/TIA-422 or EIA/TIA-485 or twisted-pair Ethernet may be monitored using a digital-storage oscilloscope, capturing data frames for close analysis of content as well as signal integrity (e.g. proper voltage levels, tolerable noise levels, etc.)....
ch_5950e16aeeb5
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Correct analysis and diagnosis of electric circuits begins with a proper understanding of some basic concepts. The following is a list of some important concepts referenced in this module's full tutorial. Define each of them in your own words, and be prepared to illustrate each of these concepts with a description of a...
ch_f4764a8f2956
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Examine the following minimalist EIA-TIA-232 serial data network and answer the following questions: [Figure image_3895: drawing; labels: TIA/EIA-232, digital, device, TD, RD, Gnd, "Null modem" cable] - Is this system capable of *simplex*, *half-duplex*, or *full-duplex* operation? - Explain why the shield wire is c...
ch_b7ca142777fd
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Decode the following EIA/TIA-232 data "frames" captured on a digital oscilloscope, each image showing a single ASCII character. Please note that each of these examples are of serial data communicated at the exact same bit rate, with a successful parity check (i.e. no corrupted bits) [Footnote: All these oscilloscope sc...
ch_b4bc61da3087
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Both EIA/TIA-422 and EIA/TIA-485 networks have the ability to operate in *multidrop mode*, where devices are connected together like this: [Figure image_3896: drawing; labels: TD(B)+, RD(B)+, RD(A)-, TD(A)-, multidrop configuration, Master, Slave, TIA/EIA-422/485 "two-wire", Gnd] However, only EIA/TIA-485 networks ar...
ch_98bf089af00f
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Is this network a EIA/TIA-422 or a EIA/TIA-485? Is it possible to tell from this diagram, and if so, how? [Figure image_3898: drawing; labels: TD(B)+, RD(B)+, RD(A)-, TD(A)-, Gnd] [Challenges] - Is this system capable of simplex communication, half-duplex communication, and/or full-duplex communication?
ch_a3d1196eddd0
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Note how the square-root term ($y$) is calculated in cell `C1`, and the denominator term ($z$) in cell `C2`. This makes the two final formulae (in cells `B1` and `B2`) simpler to interpret. The positioning of all these cells on the grid is completely arbitrary [Footnote: My personal preference is to locate all the "giv...
ch_5f4be1236152
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
*Terminating resistors* are not always necessary in EIA/TIA-485 networks, but when they are it is important to ensure their presence does not compromise biasing. Explain how termination resistors may adversely affect the biasing of a EIA/TIA-485 network, based on what you see in this schematic: [Figure image_3899: dra...
ch_0521698c7a7d
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
How long does it take to transmit a single ASCII character via an EIA/TIA-232 network operating at a bit rate of 19200 bits per second, with an 8-bit payload, odd parity, and one stop bit? How long does it take to transmit a single ASCII character via an EIA/TIA-232 network operating at a bit rate of 2400 bits per sec...
ch_6460d3832377
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
Suppose you are asked to check the integrity of a multi-conductor signal cable run between two locations. The cable has six signal conductors in it plus a shield, each one terminated at a terminal block at each end: [Figure image_3900: drawing; labels: a long distance!, Pair A, Pair B, Pair C, Multi-conductor cable, S...
ch_c27eea47cfce
question
mod_232_422_485
EIA/TIA-232, 422, and 485 Serial Networks
A data acquisition system consisting of three DAQ [Footnote: A "DAQ" module is a *Data AcQuisition* circuit that usually takes in analog or digital data from sensors and converts it into digital data readable to a computer. This functionality is not important to the question of networking.] modules connected to a perso...
ch_79b3855def34
intro
mod_50_51_relay
Overcurrent Protection Relays
Fuses were the earliest form of overcurrent protection in electric power systems, and they still fulfill this protective function remarkably well. However, very early in the development of electric power systems the shortcomings of fuses were recognized and the first overcurrent protective relays were developed as an a...
ch_c0d3d8510054
intro
mod_50_51_relay
Overcurrent Protection Relays
The following list cites concepts related to this module's topic that are easily misunderstood, along with suggestions for properly understanding them: - **Interpreting single-line diagrams** -- a common form of technical documentation in the electrical power industry is the *single-line* or *one-line* diagram, which ...
ch_344511eaf1c1
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Perhaps the most basic and necessary protective relay function is *overcurrent*: commanding a circuit breaker to trip when the line current becomes excessive. The purpose of overcurrent protection is to guard against power distribution equipment damage, due to the fact that excessive current in a power system dissipate...
ch_c2622ff494f2
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Electromechanical 50 (instantaneous overcurrent) relays are models of simplicity, consisting of nothing more than a coil [Footnote: In protective relay circuit diagrams, it is conventional to show relay coils as "zig-zag" symbols rather than as actual coils of wire as is customary in electronic schematics. Those famili...
ch_6d1ec910df46
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Electromechanical 51 (time overcurrent) relays are more complicated in design, using a rotating metal "induction disk" to physically time the overcurrent event, and trip the circuit breaker only if the overcurrent condition persists long enough. A photograph of a General Electric time-overcurrent induction-disk relay a...
ch_181e9a8219e7
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Setting a time overcurrent (51) relay consists of establishing the value of current necessary to overcome the restraining spring's torque. Any current value less than this pickup value cannot ever cause the relay to trip. In induction disk relays such as the General Electric model shown here, this pickup setting may be...
ch_178c031ca99e
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Several different curve shapes are commonly applied in overcurrent protection applications within the United States: - Moderately inverse - Inverse - Very inverse - Extremely inverse - Short-time inverse Time curves standardized by the Swiss standards agency IEC (International Electrotechnical Commission) include...
ch_cbb2dbabf974
tutorial
mod_50_51_relay
Overcurrent Protection Relays
Modern digital overcurrent relays rarely require calibration, because the analog-to-digital converter circuits responsible for converting the CT current signals into digital number values readable by the relay's microprocessor are highly reliable and unlikely to "drift" with age. Electromechanical overcurrent relays, h...
ch_64563d6eb694
tutorial
mod_50_51_relay
Overcurrent Protection Relays
## Instantaneous relay calibration Instantaneous overcurrent relays are typically adjusted by threading a ferromagnetic core into or out of the center of the relay's solenoid coil. It is common for relays of this type to provide a scale showing approximate pickup current value as a function of core position, but these...
ch_bde7cd9c4390
tutorial
mod_50_51_relay
Overcurrent Protection Relays
## Inverse time relay calibration Induction disk time delay relay calibration requires verification of two distinct parameters: *pickup* value and *time delay*. The pickup value is that amount of current passed through the relay necessary to generate an operating torque equal in magnitude to the restraining torque of ...
ch_1df2dc2620bd
historical
mod_50_51_relay
Overcurrent Protection Relays
A fascinating historical reference on protective relay systems is Victor Todd's *Protective Relays -- their theory, design, and practical operation* published in 1922. One notable detail in this book is just how closely some of the electromagnetic relay models circa 1922 resemble modern electromechanical protective rel...
ch_479eb96515e3
historical
mod_50_51_relay
Overcurrent Protection Relays
**Relay Specifications. --** In order that unreliable and unsatisfactory overload and underload relays may not be used in installations, it is always well to add the following specifications. If a relay meets these fundamental requirements and is well constructed, it should be satisfactory, but these specifications wil...
ch_71595dacb2af
question
mod_50_51_relay
Overcurrent Protection Relays
Correct analysis and diagnosis of electric circuits begins with a proper understanding of some basic concepts. The following is a list of some important concepts referenced in this module's full tutorial. Define each of them in your own words, and be prepared to illustrate each of these concepts with a description of a...
ch_12c6f429a7f0
question
mod_50_51_relay
Overcurrent Protection Relays
The following is an electrical schematic diagram for a General Electric model IAC77 electromechanical instantaneous/time-overcurrent protective relay: [Figure image_5211: drawing; labels: 1, 2, 3, Seal-in, coil, contact, 51, 50, GE model IAC77 50/51 overcurrent relay, 5, 6, 52, 52a, TC, CT, Circuit breaker, Fuse, Stat...
ch_d9d08d8ee131
question
mod_50_51_relay
Overcurrent Protection Relays
Sketch all the necessary wire connections for this set of three Westinghouse model CO-11 overcurrent relays to fulfill both the 50 and 51 ANSI/IEEE protective functions. Note that Westinghouse refers to the time-overcurrent element as "CO" and the instantaneous overcurrent element as "IIT": [Figure image_6494: drawing...
ch_8f914b71ed7e
question
mod_50_51_relay
Overcurrent Protection Relays
A very important concept in overcurrent protection is something called *coordination*. This is where overcurrent-protection devices (e.g. fuses, circuit breakers, reclosers, protective relays) closer to the power source have trip thresholds greater than protection devices farther away from the source. The rationale beh...
ch_dd64da3206ef
question
mod_50_51_relay
Overcurrent Protection Relays
Suppose a 51 (time-overcurrent) protective relay is used to provide protection for a large (3000 horsepower) electric motor. The motor runs on a line voltage of 4160 Volts, and has a full-load efficiency of 88%. The relay obtains its line current data from a set of three 400:5 current transformers on the motor's T1, T2...
ch_8b0ad0ef1ece
question
mod_50_51_relay
Overcurrent Protection Relays
The following is an electrical schematic diagram for a three-phase 50/51 overcurrent protective relay circuit, where three overcurrent relays (one for each phase of the power circuit) trip a single breaker in the event of an overcurrent fault. The power diagram on the left shows all the high-voltage components, while t...
ch_4c8e24eb9273
question
mod_50_51_relay
Overcurrent Protection Relays
Calculate the necessary time-dial setting for a 51 protective relay with an "extremely inverse" characteristic assuming a pick-up (tap setting) of 5 Amperes, a CT ratio of 1200:5, and a desired trip time of 10 seconds for a fault current value of 3.6 kA. Time dial setting = [Challenges]
ch_40f3fdd58eeb
question
mod_50_51_relay
Overcurrent Protection Relays
Calculate voltage dropped across the terminals of the protective relay during normal operation of this three-phase motor, being sure to express it as a phasor quantity. Assume a perfectly balanced system. [Figure image_6496: drawing; labels: (for each winding), AC induction motor, Transformer secondary, windings, 60 H...
ch_7ffd5529e083
question
mod_50_51_relay
Overcurrent Protection Relays
Write a computer program in a text-based language such as C, C++, or Python calculating the amount of time it will take an IEEE/ANSI-51 relay to trip given the sudden onset of an abnormally high current. Your program should input the line current value, the CT turns ratio, the relay's pick-up current rating (in seconda...
ch_77bad1637fb7
question
mod_50_51_relay
Overcurrent Protection Relays
The following diagrams document the overcurrent protection system for a feeder supplying three-phase AC power to an industrial load: [Figure image_5212: drawing; labels: Fuse, 125 VDC, 52, 51-1, 51-2, 51-3, Power diagram, Control diagram, 51-1 SI, 52a, 50-1, 51-2 SI, 50-2, 51-3 SI, 50-3, 52 TC] Suppose one day the ci...
ch_2e82336944db
question
mod_50_51_relay
Overcurrent Protection Relays
Examine this overcurrent protection system for a feeder, supplying three-phase power to a set of industrial loads from a substation bus: [Figure image_5213: drawing; labels: 52, 50-1, 51-1, 50-2, 51-2, 50-3, 51-3, 250:5, motor starter, To compressor, To pump, To fan, Bus, Feeder] Explain why 50/51 overcurrent protect...
ch_a6fdd096c4c7
intro
mod_555
555 Timer Circuits
The model 555 integrated circuit (IC) timer is a very popular product, used in a wide array of applications. It also serves well as an educational tool, teaching students how to use resistor-capacitor networks to perform practical timing functions. This module is written with the assumption that the 555 timer will be t...
ch_8b64f57c5e32
case_tutorial
mod_555
555 Timer Circuits
This demonstration circuit uses a generic 555 timer IC in a standard "DIP" package: [Figure image_6810: drawing; labels: Schematic, V_DD, 555, 1, 2, 3, 4, 6, 7, 8, Gnd, RST, +V, Out, Trig, Thresh, Disch] Research a manufacturer's *datasheet* for this timer IC to see the "pinout" diagram showing which pins on the IC p...
ch_7d322c8ca1a0
tutorial
mod_555
555 Timer Circuits
A practical category of circuits known as *oscillators* generate pulsing or alternating electrical signals useful for a great many applications. Perhaps the simplest type of oscillator is called a *relaxation oscillator*, based on the time-delayed energizing of a capacitor. A primitive relaxation oscillator is shown he...
ch_27c33348dd5b
tutorial
mod_555
555 Timer Circuits
The following diagram shows the standard pin numbering of a dual-inline integrated circuit package (DIP) as well as the internal functionality of the model 555 timer IC: [Figure image_1033: drawing; labels: 1, 2, 3, 4, 5, 6, 7, 8, Dual-Inline Package, (DIP), Ground, Out, V_CC, Discharge, Trigger, Threshold, Control, R...
ch_98c559e209c4
tutorial
mod_555
555 Timer Circuits
Here we see the 555 timer functioning as a relaxation oscillator. A graph showing the capacitor's "sawtooth" voltage waveform over time, with time markers ($t$) for each state of the 555 timer circuit, demonstrate the operation of this oscillator [Footnote: An important feature to remember about the 555 is that its `Ou...
ch_483c9172fa03
tutorial
mod_555
555 Timer Circuits
All the 555 timer's output terminal potential needs to do is rise high enough for the first CMOS gate to properly interpret it as a "high" state, and fall low enough that the CMOS gate properly interprets it as a "low" state. Any asymmetry in the 555 timer's "high" versus "low" output states is essentially hidden from ...
ch_fd933955e36a
tutorial
mod_555
555 Timer Circuits
Many other configurations of the 555 timer circuit exist. Configurations resulting in continuous oscillations such as the circuit shown above are called *astable*, because they have no stable state but rather switch periodically between two states. Configurations resulting in one stable state and one unstable (temporar...
ch_38e8f3e7007c
tutorial
mod_555
555 Timer Circuits
Inside every 555 timer IC is a three-element resistive voltage divider setting the voltage values at which the Trigger and Threshold inputs control the charging and discharging states. With the three resistors shown inside the 555 timer being of equal value, this divides the DC supply voltage into thirds, such that the...
ch_ce681ae3257b
derivation
mod_555
555 Timer Circuits
An often bewildering phenomenon for students of electronics is something called *latch-up*, known to plague certain forms of integrated circuit. "Latch-up" describes a condition where the IC suddenly ceases to function properly, and instead draws an unreasonably high amount of current from the DC power source, sometime...
ch_eb8d160c6e47
derivation
mod_555
555 Timer Circuits
Each of the doped semiconductor layers in the cross-section are noted with their respective dopant concentration levels, a "+" meaning a high concentration of dopant and "$-$" meaning a low concentration of dopant. Strongly-doped P-type and N-type layers are shown as P+ and N+, respectively. Lightly-doped P-type and N-...
ch_3c236a77610d
derivation
mod_555
555 Timer Circuits
Here we see some voltage dropped along the conductors carrying current to a heavy load ($R_{load1}$), the effect of these voltage drops being to suppress the potential of the IC's positive rail terminal slightly below that of the power source's positive terminal, and to elevate the potential of IC's negative rail termi...
ch_5171876e63d7
question
mod_555
555 Timer Circuits
Correct analysis and diagnosis of electric circuits begins with a proper understanding of some basic concepts. The following is a list of some important concepts referenced in this module's full tutorial. Define each of them in your own words, and be prepared to illustrate each of these concepts with a description of a...
ch_03e35cd22e86
question
mod_555
555 Timer Circuits
Identify which foundational concept(s) apply to each of the declarations shown below regarding the following circuit. If a declaration is true, then identify it as such and note which concept supports that declaration; if a declaration is false, then identify it as such and note which concept is violated by that declar...
ch_08446926d1d1
question
mod_555
555 Timer Circuits
The *duty cycle* of any oscillation is the ratio of "high" time to "total" period. In the case of an astable 555 timer circuit, the duty cycle of the Output terminal signal is the ratio of the 555 timer's "charging" time versus the period of the waveform (i.e. total cycle time, or "charging" plus "discharging" time). ...
ch_a4fa9659ee01
question
mod_555
555 Timer Circuits
A *sequential* timer circuit may be constructed from multiple 555 timer ICs cascaded together. Examine this circuit and determine how it works: [Figure image_1040: drawing; labels: +V, Input, pulse, Output A, Output B] Sketch a *timing diagram* showing all three pulse signals properly aligned with one another in time...
ch_6180a40e8fef
question
mod_555
555 Timer Circuits
It is common to see a capacitor connected between the "Control" terminal and ground in 555 timer circuits, especially when precise timing is important. [Figure image_2335: drawing; labels: R_1, R_2, C_1, C_2] Explain what purpose the capacitor $C_2$ serves in this circuit. [Challenges] - What operational parameters...
ch_1b13481cc6de
question
mod_555
555 Timer Circuits
Insert a bipolar junction transistor into this circuit so that the 555 timer is able to pulse a powerful electric motor on and off: [Figure image_5711: drawing; labels: R_1, R_2, C_1, Motor, 12 V, 50 V] What device parameters would we need to check in order to choose a transistor appropriate for this application? No...
ch_e28a6d2cf435
question
mod_555
555 Timer Circuits
Capacitors store energy in the form of an electric field, and this manifests as voltage between the capacitor terminals. The capacitor used in a 555 timer circuit is no exception to this, behaving as a load as it stores up energy during the "charging" portion of the cycle. Explain what becomes of this stored energy du...
ch_067d66fd22e2
question
mod_555
555 Timer Circuits
Suppose you are tasked with designing an astable 555 circuit that will be powered by a 9-Volt battery. As the battery becomes depleted of energy and its terminal voltage decreases, will the 555's oscillation frequency change? Explain why or why not. Suppose you were choosing the resistor and capacitor values for this...
ch_6952ebbb2c88
question
mod_555
555 Timer Circuits
The following circuit outputs both triangle-wave and square-wave voltage signals, using a 555 timer: [Figure image_3285: drawing; labels: +V, R, C, Q, D_1, D_2, D_3, D_4, V_out (triangle), V_out (square)] Screenshots of an oscilloscope showing the triangle and square wave outputs appear below, using a 10:1 probe. For...
ch_da662c7de21d
question
mod_555
555 Timer Circuits
The model 555 integrated circuit is a very popular and useful "chip" used for timing purposes in electronic circuits. The basis for this circuit's timing function is a resistor-capacitor (RC) network: [Figure image_1037: drawing; labels: R_1, R_2, C] In this configuration, the 555 chip acts as an *oscillator*: switch...
ch_eb1b9ec84d6b
question
mod_555
555 Timer Circuits
A popular use of the 555 timer is as a *monostable* multivibrator. In this mode, the 555 will output a pulse of fixed length when commanded by an input pulse: [Figure image_2337: drawing; labels: +V, Input, pulse, Fixed time] How low does the triggering voltage have to go in order to initiate the output pulse? Also,...
ch_8790759c0542
question
mod_555
555 Timer Circuits
In this astable 555 circuit, a load is repeatedly energized by the energy stored up within the capacitor. Calculate the quantity of energy delivered to this load with every "discharge" portion of the circuit's cycle: [Figure image_2980: drawing; labels: Load, 4k7, 270μ, 12 V] [Challenges] - Will this amount of energ...
ch_244b88beeecf
question
mod_555
555 Timer Circuits
This circuit uses a "555" integrated circuit to produce a low-frequency square-wave voltage signal (seen between the "Out" terminal of the chip and ground), which is used to turn a pair of transistors on and off to flash a large lamp. Predict how this circuit will be affected as a result of the following faults. Consid...
ch_38a8e802c8c2
question
mod_555
555 Timer Circuits
What would happen to the operation of this astable 555 timer circuit if a resistor were accidently connected between the "Control" terminal and ground? Explain the reason for your answer. [Figure image_2336: drawing; labels: R_1, R_2, C_1] [Challenges] - Does the addition of this resistor affect the output signal (p...
ch_f28dc9026bc0
question
mod_555
555 Timer Circuits
A student builds their first astable 555 timer circuit, using a TLC555CP chip. Unfortunately, it seems to have a problem. Sometimes, the output of the timer simply stops oscillating, with no apparent cause. Stranger yet, the problem often occurs at the precise time anyone moves their hand within a few inches of the cir...
ch_352e7d6009d8
question
mod_555
555 Timer Circuits
Identify at least one component fault that would cause the final 555 timer output to always remain low: [Figure image_2338: drawing; labels: +V, Input, pulse, (no pulse), R_1, C_1, C_2, R_2, R_3, C_3] For each of your proposed faults, explain *why* it will cause the described problem. [Challenges] - What purpose is...
ch_2992a5c8d5a5
intro
mod_67_relay
Directional Overcurrent Protection Relays
Applications exist in electric power systems where current flowing in one direction is normal, but it would be considered abnormal to flow in the other direction. For such applications a *direction-sensitive* current relay is appropriate. This module focuses on relays designed to detect this condition.
ch_a6089b3d482a
tutorial
mod_67_relay
Directional Overcurrent Protection Relays
While 50 and 51 (instantaneous and time overcurrent) relay functions monitor line current magnitude and guard against excesses, there are applications where the *direction* of line current is just as relevant as the magnitude. In such cases, we need a protective relay function able to discriminate between current in on...
ch_cf384d74f5ec
tutorial
mod_67_relay
Directional Overcurrent Protection Relays
Modern microprocessor-based directional relays have a definite advantage in this regard over legacy electromechanical relay designs, in being able to intelligently select the best polarizing quantity to use during fault conditions. Relays manufactured by Schweitzer Engineering Laboratories having directional protection...
ch_2844d1eaef51
intro
mod_79_relay
Reclosing Protection Relays
This module focuses on *reclosing* as a power circuit protective function: causing a circuit breaker to automatically re-close very rapidly following an automatic trip, in order to test the protected circuit for the continued presence of a fault. This protection scheme seeks to restore power as soon as possible in the ...
ch_af84fa33a1cc
tutorial
mod_79_relay
Reclosing Protection Relays
Overhead power lines are less expensive to install than underground power lines, but subject to more faults such as unintentional contact with foreign objects (e.g. tree limbs) and occasional lightning strikes. If a fault is permanent, the only safe action for a protection system to take is to trip the circuit breaker(...
ch_e2140604a1be
tutorial
mod_79_relay
Reclosing Protection Relays
The principle of automatic reclosing may be applied to transmission lines as well as distribution lines, but new challenges exist at this level of a power grid. When transmission lines serve to interconnect distributed generating stations, interruption of that line for any significant time invites generator de-synchron...
ch_039dfe6db084
historical
mod_79_relay
Reclosing Protection Relays
A fascinating historical reference on protective relay systems is Victor Todd's *Protective Relays -- their theory, design, and practical operation* published in 1922. This book contains descriptions of automatic reclosing relays (referred to as "service-restoring" relays) and circuit breakers showing the state of the ...
ch_d031e0f00a8d
tutorial
mod_86_relay
Auxiliary Protective Relays
An important type of "accessory" relay, especially for legacy electromechanical protective relays, is the so-called *auxiliary* or *lockout* relay, designated by the ANSI/IEEE number code 86. The purpose of an 86 relay is to serve as an intermediary element between one or more protective relays and one or more control ...
ch_eb3217a6f6cb
intro
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
Kirchhoff's Current Law states that the algebraic sum of all currents entering and exiting a node must be zero. This law is based on the Law of Electric Charge Conservation, and it is a fundamental principle of circuit analysis. It also happens to be the basis for an entire class of protective relays designed to detect...
ch_179b670b7d02
intro
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
The following list cites concepts related to this module's topic that are easily misunderstood, along with suggestions for properly understanding them: - **Interpreting single-line diagrams** -- a common form of technical documentation in the electrical power industry is the *single-line* or *one-line* diagram, which ...
ch_1e47d1f28213
tutorial
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
One of the fundamental laws of electric circuits is *Kirchhoff's Current Law*, which states the algebraic sum of all currents at a circuit node (junction) must be zero. This law is based on an even more fundamental law of physics: the *Conservation of Electric Charge* which states electric charges are eternal and thus ...
ch_b5f84e4be4bb
tutorial
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
A simple form of differential current protection for this generator may be implemented by connecting CTs on either side of each winding to operating coils of an electromechanical relay like this. For the sake of simplicity, protection for only one phase winding (C) of the generator will be shown. A practical differenti...
ch_9bc8a5160c1a
tutorial
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
It is noteworthy that a form of differential current protection also finds application in American households, where electrical codes require the installation of *Ground Fault Current Interruptor* (GFCI) protected circuits in areas where contact between electrical appliances and water is likely (e.g. bathrooms, kitchen...
ch_ea658c87380f
tutorial
mod_87GLB_relay
Differential Generator, Line, and Bus Protection Relays
A very important concept in the field of protective relaying is that of *protection zones*, which is easily explained in the context of differential current relays. Simply defined, a relay's "protection zone" is the physical range wherein the specified electrical fault may be detected, and thereby any components and co...