"""Single-container historical OPC UA replay runtime. Hugging Face exposes only the HTTP application port. The OPC UA server still runs inside the same container on localhost:4840, and this collector reads it through the normal OPC UA protocol before publishing a dashboard snapshot. """ from __future__ import annotations import asyncio import contextlib import os import time from datetime import datetime from pathlib import Path from typing import Any from asyncua import Client from asyncua.ua.uaerrors import BadNoData from .opcua_replay_server import run as run_replay_server def _value(data_value) -> Any: if not data_value.StatusCode.is_good(): return None return data_value.Value.Value async def _read(node) -> Any: try: return _value(await node.read_data_value()) except BadNoData: return None def build_snapshot( station: dict[str, Any], pumps: list[dict[str, Any]], ) -> dict[str, Any]: """Build the public snapshot without inventing unavailable measurements.""" total_flow = float(station.get("totalFlow") or 0.0) total_power = float(station.get("totalPower") or 0.0) running = [pump for pump in pumps if int(pump.get("status") or 0) == 1] # Individual outlet flow is not measured. Allocate only for display using # measured pump power shares and mark the provenance explicitly. weights = [max(float(pump.get("power") or 0.0), 0.0) for pump in running] if running and sum(weights) <= 0: weights = [1.0] * len(running) weight_total = sum(weights) for pump in pumps: pump["flow"] = 0.0 pump["flowSource"] = "not_running" pump["head"] = None pump["headSource"] = "missing_pressure" for pump, weight in zip(running, weights): pump["flow"] = total_flow * weight / weight_total if weight_total else 0.0 pump["flowSource"] = "estimated_power_share" pressure = station.get("pressure") historical_timestamp = station.get("replayTimestamp") return { "station": "胶州二期提升泵站(历史 OPC 回放)", "source": "historical_opc_replay", "sourceLabel": "三个月历史数据 · OPC UA 内部回放", "historicalTimestamp": historical_timestamp, "replayIndex": station.get("replayIndex"), "replayCount": station.get("replayCount"), "level": station.get("level"), "pressure": pressure, "pressureQuality": "measured" if pressure is not None else "missing", "totalFlow": total_flow, "totalPower": total_power, "sec": total_power / total_flow if total_flow > 0 else 0.0, "pumps": pumps, # Use wall-clock time for the rolling chart while retaining the original # historical timestamp above. "ts": int(time.time() * 1000), } class HistoricalOpcDemoRuntime: def __init__(self) -> None: self.latest: dict[str, Any] | None = None self.error: str | None = None self.enabled = False self._tasks: list[asyncio.Task] = [] async def start_from_env(self) -> None: source = os.environ.get("BIDITECH_DEMO_REPLAY_CSV", "").strip() if not source: return csv_path = Path(source) if not csv_path.is_file(): self.error = f"Demo replay CSV not found: {csv_path}" return endpoint = os.environ.get( "BIDITECH_DEMO_OPCUA_ENDPOINT", "opc.tcp://127.0.0.1:4840/biditech/server/", ) interval = float(os.environ.get("BIDITECH_DEMO_REPLAY_INTERVAL", "1.0")) server_endpoint = endpoint.replace("127.0.0.1", "0.0.0.0") self.enabled = True self._tasks = [ asyncio.create_task( run_replay_server(server_endpoint, csv_path, interval=interval), name="historical-opc-replay-server", ), asyncio.create_task( self._collector(endpoint), name="historical-opc-replay-collector", ), ] async def stop(self) -> None: for task in self._tasks: task.cancel() for task in self._tasks: with contextlib.suppress(asyncio.CancelledError): await task self._tasks = [] async def _collector(self, endpoint: str) -> None: await asyncio.sleep(0.5) while True: try: async with Client(url=endpoint, timeout=5) as client: await self._collect_connected(client) except asyncio.CancelledError: raise except Exception as exc: # reconnect loop is intentional self.error = f"{type(exc).__name__}: {exc}" await asyncio.sleep(1.0) async def _collect_connected(self, client: Client) -> None: station_ids = { "level": "ns=2;s=PumpStation1.Level", "totalFlow": "ns=2;s=PumpStation1.TotalFlow", "totalPower": "ns=2;s=PumpStation1.TotalPower", "pressure": "ns=2;s=PumpStation1.Pressure", "replayTimestamp": "ns=2;s=PumpStation1.ReplayTimestamp", "replayIndex": "ns=2;s=PumpStation1.ReplayIndex", "replayCount": "ns=2;s=PumpStation1.ReplayCount", } station_nodes = {key: client.get_node(node_id) for key, node_id in station_ids.items()} pump_nodes = { pump_id: { field: client.get_node(f"ns=2;s=PumpStation1.Pump{pump_id}.{node_name}") for field, node_name in { "status": "Status", "freq": "Freq", "current": "Current", "power": "Power", "runHours": "RunHours", }.items() } for pump_id in range(1, 6) } while True: station_values = { key: await _read(node) for key, node in station_nodes.items() } pumps = [] for pump_id, nodes in pump_nodes.items(): pump = {"id": pump_id} for field, node in nodes.items(): pump[field] = await _read(node) pumps.append(pump) self.latest = build_snapshot(station_values, pumps) self.error = None await asyncio.sleep(0.8) demo_runtime = HistoricalOpcDemoRuntime()