Tag,Description,Manufacturer,Model,Voltage,Phase,kVA,kW,MCA,MOCP,Refrigerant,Location
UPS-1A,Static UPS module,Northline Power Systems,NPX-750-480,480Y/277,3,750,675,,,,Electrical Room 1A
UPS-1B,Static UPS module,Northline Power Systems,NPX-750-480,480Y/277,3,750,675,,,,Electrical Room 1B
UPS-2A,Static UPS module,Northline Power Systems,NPX-750-480,480Y/277,3,750,675,,,,Electrical Room 2A
UPS-2B,Static UPS module,Northline Power Systems,NPX-750-480,480Y/277,3,750,675,,,,Electrical Room 2B
PDU-1-01,Power distribution unit,Northline Power Systems,NPD-300-415,480 / 415Y/240,3,300,,,,,Data Hall 1
PDU-1-02,Power distribution unit,Northline Power Systems,NPD-300-415,480 / 415Y/240,3,300,,,,,Data Hall 1
GEN-01,Diesel generator,Harbor Engine Works,HG-3000,13800,3,3750,3000,,,,Generator Yard
GEN-02,Diesel generator,Harbor Engine Works,HG-3000,13800,3,3750,3000,,,,Generator Yard
CRAH-1-01,Computer room air handler,Coldline Systems,CW-150-480,480,3,,,45,60,,Data Hall 1
CH-01,Air-cooled chiller,Coldline Systems,AC-1200,460,3,,,612,800,R-513A,Roof