pump / backend /tests /test_mpc.py
Codex
Deploy efficiency estimate fix cf55248
aec7019
Raw History Blame Contribute Delete
2.16 kB
from app.plant import Plant
# 海斯特站规模:单泵铭牌 Q≈850 m³/h @50Hz,5 台(三用二备)
def test_optimize_meets_target_and_saves_energy():
plant = Plant()
Q_target = 700.0
res = plant.optimizer.optimize(Q_target=Q_target)
assert res["success"]
# 变频泵可 trim 到接近目标(软约束)
assert abs(res["wp"]["Q_total"] - Q_target) < 150
# 相对全泵 50Hz 基线应节能
base = plant.baseline_all_on_50hz(Q_target)
assert res["spec_energy"] <= base.spec_energy + 1e-6
def test_freqs_within_bounds():
plant = Plant()
res = plant.optimizer.optimize(Q_target=1200.0)
for f in res["freqs"].values():
assert 20.0 - 1e-6 <= f <= 50.0 + 1e-6
def test_start_stop_penalty_prefers_continuity():
plant = Plant()
# 当前 1、2 号在运,需求恰好 2 泵满足,应保持不乱切
res = plant.optimizer.optimize(
Q_target=1350.0, current_active=[1, 2],
current_freqs={1: 50.0, 2: 50.0},
)
assert res["success"]
# 真实厂家曲线下1号泵较小;当前1+2无法达到1350,允许切换为可行组合。
assert abs(res["wp"]["Q_total"] - 1350.0) <= max(50.0, 1350.0 * 0.03)
assert res["wp"]["feasible"]
def test_rotation_prefers_least_run_hours():
plant = Plant()
# 低需求单泵场景:变频泵(1/2/5)中累计运行 h 最少的 5# 应被优先
res = plant.optimizer.optimize(
Q_target=700.0,
run_hours={1: 9000.0, 2: 9000.0, 3: 9000.0, 4: 9000.0, 5: 100.0},
)
assert res["success"]
if len(res["active"]) == 1:
assert res["active"][0] == 5
def test_higher_demand_more_pumps():
plant = Plant()
low = plant.optimizer.optimize(Q_target=700.0)
high = plant.optimizer.optimize(Q_target=1700.0)
assert high["success"]
assert len(high["active"]) >= len(low["active"])
assert len(high["active"]) >= 3 # 大需求需多台
def test_infeasible_target_is_not_recommended():
plant = Plant()
res = plant.optimizer.optimize(Q_target=10000.0, level=5.5)
assert not res["success"]
assert res["status"] == "infeasible_target"