building string | source string | building_type string | location string | timezone string | native_step string | start string | end string | n_points int64 | n_observation_points int64 | n_controllable int64 | n_observation_rows int64 | tables string | exact_duplicate_rows_removed int64 | exact_duplicate_files_removed int64 | caveats string | status string |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SB1 | Google Smart Buildings | office | Mountain View, CA | America/Los_Angeles | 5min | 2019-01-01 00:00:00+00:00 | 2024-07-31 23:55:00+00:00 | 4,470 | 1,198 | 772 | 542,592 | actions;observations;reward;reward_info | 0 | 0 | rebuilt from raw logs; real missing values + validity mask; whole-day BMS outages (e.g. 93/213 days in 2024) | built |
SB2 | Google Smart Buildings | office | Mountain View, CA | America/Los_Angeles | 5min | 2019-01-01 00:00:00+00:00 | 2024-07-31 23:55:00+00:00 | 3,136 | 1,396 | 4 | 587,726 | actions;observations;reward;reward_info | 812 | 48 | values integer-truncated and zero-filled by the source export (not recoverable); mixed degF/K | built |
SB3 | Google Smart Buildings | office | Mountain View, CA | America/Los_Angeles | 5min | 2020-01-01 00:00:00+00:00 | 2020-12-31 23:55:00+00:00 | 13,610 | 8,075 | 6 | 105,408 | actions;observations;reward;reward_info | 568 | 0 | 2020 only; integer-truncated and zero-filled by source; most channels all-zero | built |
SB4 | University collaboration | academic / research | Syracuse, NY | America/New_York | 5min | 2023-12-08 16:25:00+00:00 | 2026-04-02 04:00:00+00:00 | 8,600 | 8,600 | 0 | 159,231 | observations | 300,718 | 0 | whole-building BAS panels; three overlapping source exports merged; provider point notes applied as flags | built |
SB5 | University collaboration | residential (retrofit study) | Syracuse, NY | America/New_York | 1min | 2021-08-02 14:21:00+00:00 | 2023-05-09 23:25:00+00:00 | 477 | 477 | 0 | 838,222 | observations | 0 | 0 | 8 units + shared site weather; before/after retrofit periods | built |
SB6 | University collaboration | laboratory | Syracuse, NY | America/New_York | 5min | 2022-10-02 19:40:00+00:00 | 2025-01-13 11:55:00+00:00 | 1,078 | 1,078 | 0 | 192,095 | observations | 1 | 0 | single-floor lab with a dedicated AHU and 13 VAVs, located on the 4th floor of SB4 | built |
SB7 | Campus BAS | academic | Needham, MA | America/New_York | 15min | 2019-06-13 00:00:00+00:00 | 2024-07-12 15:30:00+00:00 | 1,005 | 1,005 | 0 | 164,429 | observations | 352,327 | 0 | null | built |
SB8 | Campus BAS | student center (dining) with central plant | Needham, MA | America/New_York | 15min | 2018-05-30 08:30:00+00:00 | 2024-07-12 14:45:00+00:00 | 758 | 758 | 240 | 168,217 | observations | 52,022 | 0 | includes the central plant that shares its floor plans; 6 points exported by both trend sets merged | built |
SB9 | Campus BAS | academic | Needham, MA | America/New_York | 15min | 2019-06-13 00:00:00+00:00 | 2024-07-10 22:30:00+00:00 | 918 | 918 | 0 | 164,112 | observations | 208,795 | 0 | null | built |
SB10 | Campus BAS | residence hall | Needham, MA | America/New_York | 15min | 2019-06-13 00:00:00+00:00 | 2024-07-13 17:45:00+00:00 | 1,358 | 1,358 | 0 | 175,826 | observations | 470,842 | 0 | null | built |
SB11 | Campus BAS | residence hall | Needham, MA | America/New_York | 15min | 2020-04-13 20:30:00+00:00 | 2024-07-12 23:00:00+00:00 | 500 | 500 | 0 | 127,693 | observations | 455,780 | 0 | null | built |
Smart Buildings Dataset (SB1–SB11)
Operational data from 11 buildings, 3 sources, 2018–2026: building automation system (BAS)
sensors, setpoints, commands and status, plus RL-style actions and rewards for the three Google
buildings. Every building is stored at its native time resolution with values exactly as
recorded, in native units. A single channel table (points.parquet) describes every channel
in the same vocabulary across buildings.
Buildings
| Building | Source | Type | Location | Native step | Span (UTC) | Channels |
|---|---|---|---|---|---|---|
| SB1 | Google Smart Buildings | office | Mountain View, CA | 5 min | 2019-01 → 2024-07 | 4,470 |
| SB2 | Google Smart Buildings | office | Mountain View, CA | 5 min | 2019-01 → 2024-07 | 3,136 |
| SB3 | Google Smart Buildings | office | Mountain View, CA | 5 min | 2020 | 13,610 |
| SB4 | University collaboration | academic / research | Syracuse, NY | 5 min | 2023-12 → 2026-04 | 8,600 |
| SB5 | University collaboration | residential (retrofit study) | Syracuse, NY | 1 min | 2021-08 → 2023-05 | 477 |
| SB6 | University collaboration | laboratory | Syracuse, NY | 5 min | 2022-10 → 2025-01 | 1,078 |
| SB7 | Campus BAS | academic | Needham, MA | 15 min | 2019-06 → 2024-07 | 1,005 |
| SB8 | Campus BAS | student center (dining) with central plant | Needham, MA | 15 min | 2018-05 → 2024-07 | 758 |
| SB9 | Campus BAS | academic | Needham, MA | 15 min | 2019-06 → 2024-07 | 918 |
| SB10 | Campus BAS | residence hall | Needham, MA | 15 min | 2019-06 → 2024-07 | 1,358 |
| SB11 | Campus BAS | residence hall | Needham, MA | 15 min | 2020-04 → 2024-07 | 500 |
Building IDs match Table 1 of the paper. buildings.csv has the authoritative numbers.
Layout
buildings.csv one row per building
points.parquet channel table for all buildings (also SBx/points.csv)
loader.py reference loader
SBx/timeseries/<table>/<year>.parquet wide table: UTC index "timestamp", one column per channel
SBx/timeseries/<table>/<year>.irregular.parquet long table (timestamp, point_id, value): samples off the native grid
SBx/timeseries/<table>/<year>.<aux>.parquet auxiliary tables (see below)
SBx/provenance.json inputs with sha256, processing steps, removal log
SBx/metadata/ floor plans, device/zone info where available
Tables: SB1–SB3 have observations, actions, reward_info, reward; all other buildings have
observations only (whether a channel is controllable is a channel-table attribute).
Auxiliary tables:
observations/<year>.valid(SB1): per-reading validity flag from the source (1 valid, 0 invalid, −1 not reported).observations/<year>.offset(SB1): ns between each reading's own timestamp and the 5-min step.actions/<year>.status(SB1): action response type (1 = accepted; seesmart_control_building.proto).<year>.text: free-text values (e.g. SB1 action response messages).<year>.meta: per-row metadata;dup_index > 0marks a repeated timestamp with different values.<year>.index(SB7–SB11): the BAS record number of each sample (SB8:<point>#plant_exportholds the central-plant export's record numbers for the 6 points both exports share).<year>.rowinfo(SB4, SB5, SB6): maps every source line to its stored row (source file, line, original local time).
Principles
- Nothing removed except exact duplicates. Rows that repeat a timestamp with identical values
in every column, and byte-identical copies of files, were removed; counts are in
buildings.csvand eachprovenance.json. Everything else is kept, including all-zero, alarm and label channels, and repeated timestamps with differing values. - No resampling. Off-grid samples are kept in
.irregulartables, not snapped or interpolated. - Missing is NaN. Never 0. The exception is data the source itself zero-filled (SB2/SB3; see caveats), where zeros are kept as recorded and flagged.
- Native units.
points.unitgives the recorded unit,points.to_sithe conversion. The loader converts on request (si=True).
Channel table (points.parquet)
point_id (column name in the timeseries), building, table, source_name, description,
equipment, equipment_type, kind (sensor / setpoint / command / status / alarm / meter / calc /
label / unknown), quantity (temperature, airflow, co2, pressure, power, …), unit, to_si,
precision, value_type, value_labels, controllable, n_samples, frac_missing, all_zero,
constant, first_valid, last_valid, flags, notes.
Classification (equipment, kind, quantity) is rule-based from source names; when the rules
don't match, the value is unknown rather than a guess.
Common flags: zero_filled_source, integer_truncated_source, zero_means_missing,
few_distinct_values, unit_unknown, unit_header_conflict, unit_quantity_mismatch,
confused_in_source_sheet, exclude_suggested:<reason>.
Loading from Hugging Face
from datasets import load_dataset
points = load_dataset("Jgoldfeder/smart-buildings", "points", split="train").to_pandas()
sb4 = load_dataset("Jgoldfeder/smart-buildings", "SB4_observations", split="train") # all years
Each SBx_<table> configuration is one building's wide table (all years). Auxiliary tables
(validity masks, off-grid samples, row metadata) are not exposed as configurations; get them with
the full download and loader.py:
from huggingface_hub import snapshot_download
path = snapshot_download("Jgoldfeder/smart-buildings", repo_type="dataset") # ~6 GB
# or only one building: snapshot_download(..., allow_patterns=["SB1/*", "*.csv", "*.parquet", "loader.py"])
import sys; sys.path.insert(0, path); import loader as sb
df = sb.load("SB1", start="2023-01-01", end="2023-02-01", si=True)
Usage (local copy)
import loader as sb
sb.buildings()
pts = sb.points("SB1")
zone_temps = pts[(pts.table == "observations") & (pts.quantity == "temperature") & (pts.kind == "sensor")].point_id
df = sb.load("SB1", points=zone_temps, start="2023-01-01", end="2023-02-01", si=True) # degC
Caveats
- SB2 and SB3: precision lost at the source. Google's export stored observations, actions and
reward info as integers (truncated toward zero) and replaced missing values with 0; the raw logs
are not available, so this cannot be undone. Rewards are exact. Applying the same truncation to
clean SB1 data shows temperatures in °F lose 0.62 °F on average (≈7.5% of a channel's std,
correlation 0.9999 retained); airflow, CO2, occupancy and positions are nearly unaffected;
channels with values in (0, 1) collapse (flagged
few_distinct_values). Seeanalysis/truncation_damage_sb1_2023.csv. - SB2 early years are mostly zero-fill. Fraction of zone-temperature readings that are real
(non-zero) by year: 2019 4%, 2020 36%, 2021 78%, 2022 94%, 2023 80%, 2024 75%. Use
mask_zero_fills=True(or thezero_means_missingflag) before training on SB2/SB3; without it, zero-filled kelvin temperatures convert to −273 °C. - SB1: building-system outages. SB1 is rebuilt from the raw logs with the source's validity flags. Whole days are invalid in places (e.g. 93 of 213 days in 2024). Google's earlier public SB1 tables stored these as 0 (49% of cells in its 2024 partition).
- SB1–SB3 units differ by device. In SB1, VAV-level devices record °F and CFM, while AHU/plant devices record K, m³/s and Pa; SB2/SB3 mix °F and K. Units are assigned per channel and verified against recorded ranges.
- Campus (SB7–SB11) units. Taken from the source trend sheet, with conflicts and unknowns flagged (e.g. temperatures logged in volts in SB10). Controllability is marked in the source only for SB8 (student center and its central plant).
- SB4 and SB6 come from one export of the same campus BAS: SB4 is the whole building (16 controller
panels, three overlapping exports merged; the newest contains every row of the other two) and SB6 is the
laboratory, a single-floor laboratory on SB4's 4th floor with its own AHU and 13 VAVs. Rows of the panel files
sharing a timestamp are combined when every shared channel is identical; genuinely conflicting rows are kept
with
dup_index. The provider's point-selection notes are applied only as flags. - SB5 has 8 residential units (channels
UNIT<n>.*) and shared site weather (SITE.*); the retrofit phase (before/after) is inmeta.parquet. - SB8 combines the student center and the central plant that shares its floor plans (74,631 sq ft in total). Six points appear in both source exports with identical values and are stored once.
- Timezones. All timestamps are UTC. Campus sources logged local time with EST/EDT; SB4–SB6 sources
logged naive local time, converted as documented in
provenance.json.
Provenance
Each SBx/provenance.json lists every input file with its sha256, every processing step, and the
exact-duplicate removal counts. Conversion and validation code is in code/.
License
Creative Commons Attribution 4.0 International (CC BY 4.0). SB1–SB3 derive from the Google Smart Buildings data; please also credit that source when using them.
Citation
If you use this dataset, please cite:
@article{goldfeder2024smart,
title={The smart buildings control suite: A diverse open source benchmark to evaluate and scale hvac control policies for sustainability},
author={Goldfeder, Judah and Dean, Victoria and Jiang, Zixin and Wang, Xuezheng and Lipson, Hod and Sipple, John and others},
journal={arXiv preprint arXiv:2410.03756},
year={2024}
}
- Downloads last month
- 230