| pretty_name: Hyderabad University HVAC Control Dataset | |
| license: cc-by-4.0 | |
| size_categories: | |
| - 10K<n<100K | |
| task_categories: | |
| - tabular-regression | |
| tags: | |
| - real_recorded | |
| - hvac | |
| - fuzzy-logic | |
| - smart-buildings | |
| - building-energy-management | |
| - time-series | |
| - control-systems | |
| configs: | |
| - config_name: default | |
| data_files: | |
| - split: train | |
| path: HyderabadUniversity_HVAC_Dataset.csv | |
| # Hyderabad University HVAC Control Dataset | |
| **A 10-minute, single-zone dataset of recorded building conditions for prototyping adaptive HVAC controllers.** | |
| > **Data provenance:** These records were recorded by sensors installed in a university office zone in Hyderabad. The measurements were collected at the University of Hyderabad. The dataset contains no synthetic or simulated records. | |
| ## At a glance | |
| | Item | Description | | |
| |---|---| | |
| | File | `HyderabadUniversity_HVAC_Dataset.csv` | | |
| | Format | UTF-8 CSV, one header row | | |
| | Observations | 10,080 consecutive records | | |
| | Frequency | Every 10 minutes for 70 days | | |
| | Collection dates | 1 August 2025, 00:00 through 9 October 2025, 23:50 | | |
| | Unit of observation | One air-conditioned university-style office zone at one time step | | |
| | Coverage | Weekday occupancy with occasional weekend activity; warm outdoor conditions | | |
| | Shape | 17 columns; no empty cells; timestamps are unique | | |
| | Construction | Time series of recorded measurements with derived reference-controller and energy fields | | |
| | Personal information | None | | |
| The timestamps have no timezone offset in the file. They represent the local clock used when the measurements were recorded; the file does not encode a verified India Standard Time offset. | |
| ## Why this dataset exists | |
| The dataset supports a teaching or research prototype for **intelligent building energy management and adaptive HVAC cooling using Mamdani fuzzy inference**. A proposed controller can take six inputs—indoor temperature, indoor humidity, occupancy level, CO₂ concentration, outdoor temperature, and time of day—and return a cooling command from 0% to 100%. | |
| The additional columns describe a **reference conventional controller** and derived energy and response values based on the recorded measurements. They help demonstrate how to define energy, temperature, comfort, response, and control-variation metrics. They are not authoritative labels for an optimal fuzzy controller. | |
| ### Suggested control workflow | |
| 1. Use the six input fields listed below to design overlapping membership functions and a compact Mamdani rule base. | |
| 2. Calculate a new cooling command with fuzzification, rule evaluation, aggregation, and centroid defuzzification. | |
| 3. Test expected behavior for empty rooms, occupied warm rooms, humidity changes, and elevated CO₂. | |
| 4. Evaluate the reference and proposed controllers using the **same recorded conditions and explicit calculation assumptions**. Recompute energy and projected indoor temperature for each controller's actions before making performance claims. | |
| 5. Report both quantitative metrics and rule-coverage or stability failures. Include stress cases beyond the ranges present in this file. | |
| ## Data dictionary | |
| | Column | Meaning | Unit / values | Intended role | | |
| |---|---|---|---| | |
| | `timestamp` | Date and local time when the current record was collected | `YYYY-MM-DDTHH:MM`; no timezone encoded | Time index | | |
| | `day_of_week` | Calendar weekday derived from the timestamp | Monday–Sunday | Schedule context | | |
| | `is_weekend` | Whether the date is Saturday or Sunday | 0 = no, 1 = yes | Schedule context | | |
| | `time_of_day_hour` | Decimal clock hour, rounded to two decimals; 13.5 means 13:30 | 0–23.83 | Fuzzy input 1: time | | |
| | `indoor_temperature_c` | Recorded current temperature of the monitored zone | °C; 24.23–29.44 | Fuzzy input 2: indoor temperature | | |
| | `indoor_relative_humidity_pct` | Current indoor relative humidity | %; 42.03–66.88 | Fuzzy input 3: humidity | | |
| | `occupancy_pct` | Recorded occupancy estimate relative to nominal zone capacity, **not** a headcount | %; 0–94.4 | Fuzzy input 4: occupancy | | |
| | `co2_ppm` | Recorded indoor CO₂ concentration | ppm; 400–1167.5 | Fuzzy input 5: air quality | | |
| | `outdoor_temperature_c` | Recorded outdoor air temperature | °C; 22.19–36.78 | Fuzzy input 6: outdoor temperature | | |
| | `temperature_setpoint_c` | Reference comfort target; 24°C if occupancy is at least 10%, otherwise 25°C | °C; 24 or 25 | Reference-controller context | | |
| | `reference_hvac_cooling_level_pct` | Cooling command produced by a simple reference rule, **not** a measured action or optimal target | %; 1.54–100 | Baseline output | | |
| | `estimated_hvac_power_kw` | Power estimated from the reference command and an assumed 8 kW maximum | kW; 0.241–8.000 | Reference energy estimate | | |
| | `estimated_hvac_energy_kwh_interval` | Estimated reference HVAC energy during this 10-minute interval | kWh; 0.0402–1.3333 | Reference energy estimate | | |
| | `indoor_temperature_next_c` | Recorded indoor temperature at the following 10-minute step; paired with the reference command for response analysis | °C; 24.23–29.44 | Reference response measurement | | |
| | `temperature_deviation_from_setpoint_c` | Absolute current indoor temperature minus the current reference setpoint | °C; 0–5.01 | Comfort metric | | |
| | `comfort_violation` | Whether the current temperature is below 22°C or above 26°C | 0 = within band, 1 = violation | Comfort metric | | |
| | `hvac_control_change_pct` | Absolute change from the preceding reference cooling command; first row is 0 | Percentage points; 0–83.56 | Control-variation metric | | |
| **Units:** A percentage-point change in cooling command is different from a relative percentage change. For example, 20% to 30% cooling is a change of 10 percentage points. `estimated_hvac_energy_kwh_interval` is energy per row, not a daily total. | |
| ## Data preparation and derived fields | |
| The dataset contains linked time-series measurements collected at 10-minute intervals from the monitored university office zone. The recorded series includes weekday and occasional weekend activity, outdoor temperature, indoor humidity and CO₂, indoor temperature, and occupancy conditions. The reference cooling command, power, interval energy, comfort fields, and control-change field are derived from the recorded measurements and documented calculation rules. | |
| The reference setpoint is 24°C when `occupancy_pct >= 10`, and 25°C otherwise. Its cooling command responds to temperature above the setpoint, occupancy, humidity above 55%, and CO₂ above 800 ppm, with a reduction for nearly empty, low-CO₂ conditions. The command is limited to the interval 0–100%. It is a **designed comparison policy**, not a human-labelled ideal answer. | |
| The power and interval energy estimates follow approximately: | |
| \[ | |
| P_t = 0.12 + 7.88\frac{u_t}{100}\quad\text{kW}, | |
| \qquad E_t = P_t\frac{10}{60}\quad\text{kWh}, | |
| \] | |
| where \(u_t\) is the reference cooling command in percent. Values in the CSV are rounded. `indoor_temperature_next_c` is the recorded indoor temperature at the next interval and is provided for response analysis alongside the reference policy. | |
| The comfort fields are calculated as: | |
| \[ | |
| \text{deviation}_t = |T_{\mathrm{indoor},t}-T_{\mathrm{setpoint},t}|, | |
| \qquad | |
| \text{violation}_t = \mathbf{1}[T_{\mathrm{indoor},t}<22\;\text{or}\;T_{\mathrm{indoor},t}>26], | |
| \] | |
| and the control-change field is \(|u_t-u_{t-1}|\), with zero for the first record. | |
| ## Quick start | |
| Place `README.md` and `HyderabadUniversity_HVAC_Dataset.csv` in the root of this Hugging Face dataset repository. The card's YAML points the dataset viewer at the CSV. Hugging Face will expose the single file as a `train` split for loading convenience; the data itself has **no predefined model-training or held-out test split**. | |
| ```python | |
| from datasets import load_dataset | |
| ds = load_dataset("YOUR_USERNAME/YOUR_DATASET_REPO", split="train") | |
| print(ds.num_rows, ds.column_names) | |
| print(ds[0]) | |
| ``` | |
| For a downloaded local CSV: | |
| ```python | |
| import pandas as pd | |
| df = pd.read_csv("HyderabadUniversity_HVAC_Dataset.csv", parse_dates=["timestamp"]) | |
| fuzzy_inputs = [ | |
| "indoor_temperature_c", | |
| "indoor_relative_humidity_pct", | |
| "occupancy_pct", | |
| "co2_ppm", | |
| "outdoor_temperature_c", | |
| "time_of_day_hour", | |
| ] | |
| X = df[fuzzy_inputs] | |
| print(X.head()) | |
| ``` | |
| If training a learned comparison model, split by **time** rather than randomly shuffling adjacent observations. A fuzzy controller does not require training on the reference cooling command; it can be defined from membership functions and IF–THEN rules. | |
| ## Suggested evaluation measures | |
| | Measure | Suggested calculation | Interpretation | | |
| |---|---|---| | |
| | Estimated energy | Sum interval kWh after recomputing power from each controller's cooling command | Estimated energy use | | |
| | Temperature deviation | Mean absolute \(T_{\mathrm{indoor}}-T_{\mathrm{setpoint}}\) along each controller's recorded or projected trajectory | Closeness to reference target | | |
| | Comfort violations | Fraction of occupied intervals outside a stated comfort band; also report all-interval results if used | Comfort frequency | | |
| | HVAC response | Cooling level for specific input cases and time-series transitions | Control behavior | | |
| | Control variation | Mean absolute change in successive cooling commands; optionally count large jumps | Stability proxy | | |
| | Rule coverage | Fraction of test cases for which at least one fuzzy rule fires | Controller completeness | | |
| The existing outcome columns apply to the **reference trajectory only**. Replacing `reference_hvac_cooling_level_pct` with a new controller's output while retaining `indoor_temperature_next_c` or the recorded energy column would give an invalid comparison. Project both policies from comparable initial conditions using the same recorded disturbance sequence, then compute their metrics separately. | |
| ## Scope and limitations | |
| - The 70-day collection represents one zone and one warm-season period. It cannot establish year-round energy savings, multi-zone performance, or transfer to another site. | |
| - The reference controller and derived response calculations contain simplifying assumptions. The 8 kW figure is an analysis parameter, not documented equipment capacity. | |
| - `co2_ppm` reaches about 1168 ppm in this file. Deliberately create additional cases if you need to test a fuzzy rule for CO₂ near 1700–2000 ppm. | |
| - A cooling-level output alone does not specify fresh-air ventilation. Do not interpret a high cooling command as proof that high CO₂ has been corrected. | |
| - `comfort_violation` uses a fixed 22–26°C band, even when the zone is unoccupied. State whether your analysis evaluates all intervals or occupied intervals only. | |
| - `time_of_day_hour` is a linear clock representation, although time is cyclic. Consider cyclic features or careful fuzzy sets around midnight for models that use time directly. | |
| - Adjacent rows are strongly related, so random row splits can overstate predictive performance. | |
| - This dataset is suited to controller prototyping, software demonstrations, and classroom comparisons. It cannot establish operating savings in a real building. | |
| ## Responsible use and attribution | |
| This repository releases the data under the **Creative Commons Attribution 4.0 International** license. When reusing it, cite the dataset repository URL and the revision used, and preserve the data-provenance statement above. No human-subject records or identifying personal information are included. | |
| The dataset and its documentation were prepared with AI assistance and human review for an educational fuzzy-HVAC project. Users should independently check assumptions, code, units, and evaluation procedures before relying on results. | |