Datasets:
source_record dict | normalized_inputs dict | computed_result dict | verification_result dict |
|---|---|---|---|
{
"boiler_conditions": {
"operating_pressure": 850,
"maximum_allowable_working_pressure": 1000,
"pressure_unit": "kPa(g)",
"boiler_type": "Packaged water-tube steam boiler"
},
"device_conditions": {
"device_type": "Spring-loaded safety valve",
"set_pressure": 950,
"capacity_unit": "kg/... | {
"normalized_operating_pressure": 0.85,
"normalized_pressure_unit": "MPa(g)",
"normalized_set_pressure": 0.95,
"normalized_capacity_unit": "kg/h"
} | {
"quantity_name": "Minimum required relief capacity",
"value": 2640,
"unit": "kg/h",
"calculation_steps": [
"Convert operating pressure: 850 kPa(g) ÷ 1,000 = 0.85 MPa(g).",
"Convert valve set pressure: 950 kPa(g) ÷ 1,000 = 0.95 MPa(g).",
"Apply the supplied capacity rule: 1.10 × 2,400 kg/h = 2,640 ... | {
"is_correct": true,
"value_difference": 0,
"unit_matches": true,
"verification_notes": "The submitted value equals the reference value in kg/h. The absolute difference is 0, within the stated tolerances."
} |
{
"boiler_conditions": {
"operating_pressure": 12,
"maximum_allowable_working_pressure": 16,
"pressure_unit": "bar(g)",
"boiler_type": "Industrial fire-tube steam boiler"
},
"device_conditions": {
"device_type": "Direct spring safety valve",
"set_pressure": 15.5,
"capacity_unit": "lb/h... | {
"normalized_operating_pressure": 1.2,
"normalized_pressure_unit": "MPa(g)",
"normalized_set_pressure": 1.55,
"normalized_capacity_unit": "lb/h"
} | {
"quantity_name": "Minimum required relief capacity",
"value": 2250,
"unit": "lb/h",
"calculation_steps": [
"Convert operating pressure: 12 bar(g) × 0.1 = 1.2 MPa(g).",
"Convert valve set pressure: 15.5 bar(g) × 0.1 = 1.55 MPa(g).",
"Apply the supplied capacity rule: 1.25 × 1,800 lb/h = 2,250 lb/h.... | {
"is_correct": false,
"value_difference": 50,
"unit_matches": true,
"verification_notes": "The unit matches, but the submitted value is 50 lb/h below the reference. This exceeds the 5 lb/h absolute tolerance and the 0.2% relative tolerance."
} |
{
"boiler_conditions": {
"operating_pressure": 1.6,
"maximum_allowable_working_pressure": 2,
"pressure_unit": "MPa(g)",
"boiler_type": "Once-through steam generator"
},
"device_conditions": {
"device_type": "Pilot-operated relief valve",
"set_pressure": 1.9,
"capacity_unit": "kg/h",
... | {
"normalized_operating_pressure": 1.6,
"normalized_pressure_unit": "MPa(g)",
"normalized_set_pressure": 1.9,
"normalized_capacity_unit": "kg/h"
} | {
"quantity_name": "Minimum required relief capacity",
"value": 3348,
"unit": "kg/h",
"calculation_steps": [
"Operating pressure is already in the calculation unit: 1.6 MPa(g).",
"Valve set pressure is already in the calculation unit: 1.9 MPa(g).",
"Apply the supplied capacity rule: 1.08 × 3,100 kg/... | {
"is_correct": true,
"value_difference": 0,
"unit_matches": true,
"verification_notes": "After converting the submitted rate to kg/h, it equals the reference value. The converted unit is equivalent and the difference is within both stated tolerances."
} |
Boiler Relief Device Calculation Answer Verification Dataset
This dataset uses JSON records to capture boiler operating conditions, equipment constraints, design assumptions, applicable rules, relief-device calculation questions, submitted answers, and reference answers. It also provides normalized inputs, independently calculated results, and answer comparisons for evaluating whether responses meet the stated conditions and rules. The content focuses on capacity, pressure, and unit-related calculations for safety valves and other relief devices, supporting engineering review and automated model evaluation for industrial boilers.
Introduction
Evaluate engineering models with traceable inputs, independent calculation results, and answer checks for boiler relief-device sizing.
Dataset details
- Sample rows in this repo: 3
- Full dataset size: 3382 piece
- Full dataset file size: 0.19 GB
- Modality: text
- Language: en
- Industry: Industrial Boilers & Heating Equipment
Upload this folder to a Hugging Face dataset repository. samples.jsonl is the sample split. The full dataset size above is the listing size, not the number of rows in the file.
Fields
| Field | Description |
|---|---|
source_record |
{'title': 'Source Record', 'description': 'Original input record containing boiler conditions, design assumptions, applicable rules, the question, the submitted answer, and the reference answer.'} |
normalized_inputs |
{'title': 'Normalized Inputs', 'description': 'Derived values converted to consistent units for use in the verification calculation.'} |
computed_result |
{'title': 'Computed Sizing Result', 'description': 'Independently calculated relief-device sizing result based on the source conditions and applicable rule.'} |
verification_result |
{'title': 'Answer Verification Result', 'description': 'Comparison of the submitted answer with the reference answer, evaluated against applicable tolerances.'} |
FAQ
What does the dataset contain?
Records include boiler operating conditions, equipment constraints, design assumptions, applicable rules, calculation questions, submitted answers, and reference answers. Structured fields also provide normalized inputs, independent calculation results, and answer verification results.
Which capabilities can this dataset evaluate?
It can support evaluation of model calculations and responses to relief-device capacity and pressure questions, as well as unit normalization, rule checking, and comparison against reference results. It can assist engineering review but does not replace qualified professional review or safety validation.
What format is used to deliver the data?
The data is organized as JSON, with fields for source records, normalized inputs, computed results, and answer verification results. Confirm the file count, delivery method, and available versions on the product page or in the delivery details.
What are the licensing terms?
The permitted uses and restrictions are determined by the license terms listed on the product page or agreed by the parties. Confirm the applicable terms before commercial deployment, redistribution, or use in safety-critical settings.
For more dataset information, please visit https://www.mobiusi.com or email contact@mobiusi.com
- Downloads last month
- 69